MEPVirtual Engineering Labs - Access Control & Physical Security EngineeringELV-307

Master virtual lab for electronic access control and physical security on real buildings: architectures, credentials, door hardware, wiring, interlocks, lifts, turnstiles, lock power, intrusion, fire release, schedules, commissioning and authority compliance. Written the way a commissioning lead walks a door: what the drawing says, what the site actually built, and what fails the SIRA or Civil Defence witness test.

Section 1 of 25

1. Fundamentals & System Architectures

Every access control system, from a 4-door clinic to a 2,000-door tower, does the same four things: identify the person (credential), decide (controller database and rules), act (release the lock) and report (door state back to the head-end). Where the decision is made is what separates a robust system from one that locks the building when the server reboots.

Click any block in the hierarchy

Each block shows what it does, where it lives on site, what cable feeds it and what typically goes wrong at handover.

Network loss test (do this at every SAT)

Pull the uplink and present cards. A properly designed system keeps granting from the controller's local database and buffers events.

Architecture comparison

Item2-Tier3-TierCloud-hosted
Where the grant decision is madeIntelligent door controller (local DB)ACU holds DB, RSI/sub-controller is only an I/O and reader interfaceEdge controller caches DB, cloud holds master
Typical busTCP/IP from controller to serverTCP/IP to ACU, RS-485 from ACU to RSIsEncrypted outbound TLS from edge to cloud
Offline behaviourFull: grants, APB local, buffers eventsACU offline: RSIs drop to degraded mode (facility code only or locked)Edge keeps cached DB, schedule and events; changes wait for reconnection
Best fitMid-size commercial, hotels, retailLarge campuses, high-rise with many doors per riserMulti-site retail, small offices, portfolio owners
Site snag I see mostControllers all on one unmanaged switch with no UPSRS-485 run without termination, RSI addresses duplicatedCustomer IT blocks outbound ports, nobody owns the firewall rule

Reader protocol: Wiegand vs OSDP v2.2

ParameterWiegand 26 / 34 / 37-bitOSDP v2.2 (IEC 60839-11-5)
Physical layerD0 / D1 open collector, 5 V pulsesRS-485 half duplex, differential pair
Max distanceAbout 150 m (500 ft) with 18 AWG, less with 22 AWG1,200 m (4,000 ft) on twisted pair
Cores needed6 to 8 (D0, D1, +V, 0V, LED, buzzer, hold, shield)4 (A, B, +V, 0V) plus shield
TopologyPoint to point, one reader per portMulti-drop, up to 126 addresses per bus (practical 4 to 8 readers per port)
DirectionOne way, reader to panelBidirectional: panel polls, reader reports, LED/buzzer/text commands
SecurityClear text, card number can be sniffed and replayed with a cheap tapSecure Channel AES-128, session keys, MAC per message
Tamper / supervisionNone. Cut wires look like an idle readerReader is polled; offline or tamper alarms within seconds
Consultant positionAccept only for retrofit or low-risk internal doorsSpecify as default for all new readers, Secure Channel enabled at SAT
Commissioning trap: OSDP readers often ship with Secure Channel off and the default SCBK-D key. If you do not see the "secure" flag in the head-end reader status, it is running plain OSDP. Insist on it in the SAT sheet.

Wiegand frame builder (see why Wiegand is weak)

ParityFacility codeCard number

2. Credential Technologies & Mobile Access

The credential is the weakest link on most projects I review. Specs say "smart card" and the contractor supplies MIFARE Classic because the old card printer supports it. Name the technology, the key management and the reader configuration in the spec, then check the sample card at submittal stage.

Card technologies

TechnologyFrequencySecurityClone riskNotes for submittal review
125 kHz Proximity (HID Prox, EM4100)125 kHz LFNone. Fixed ID broadcastHigh: cloned in seconds with a handheld copierReject on new projects. Allow only as dual-tech card during migration.
MIFARE Classic 1K/4K13.56 MHz HFCrypto1 (broken since 2008)High: keys recovered offlineReading UID only is worse than prox. Not acceptable for secure doors.
MIFARE DESFire EV113.56 MHzAES-128 / 3DES, mutual authLow if diversified keys usedFine for most commercial work. Confirm the reader reads the secure file, not the UID.
MIFARE DESFire EV2 / EV313.56 MHzAES-128, proximity check, transaction MACVery lowPreferred for new builds. EV3 adds secure dynamic messaging. Multi-application (canteen, lockers, printing).
HID iCLASS (legacy)13.56 MHzGlobal master key, compromisedHighTreat like prox. Migrate to iCLASS SE or Seos.
HID iCLASS SE / Seos13.56 MHzSIO data object, AES-128, Seos secure messagingVery lowCheck if the project uses HID elite keys (site-specific) or standard keys. Elite is recommended for high-security clients.

Mobile credentials

BLE (Bluetooth Low Energy)

Phone talks to reader over BLE. Read range adjustable from about 10 cm (tap mode) to several metres (hands-free / gesture "twist and go"). Good for car park barriers and accessible doors.

Watch for: reader range set too long, so a person walking past opens the door. Set range per door at commissioning and record it.

NFC

Phone emulates a card (HCE) or uses the secure element. Range 0 to 5 cm, same user habit as a card. Works with phone locked on most platforms (express mode).

Watch for: reader firmware must support the mobile credential applet, older 13.56 MHz readers do not.

Wallet provisioning

Employee badge in Apple Wallet or Google Wallet. Provisioned from the access control or identity platform, revoked remotely. Usually works for a few hours after the phone battery dies (power reserve).

Watch for: licence model per user per year. Put it in the tender BOQ, not as an afterthought.

Biometrics

ModalityHow it readsTypical vendor FAR / FRRSpoof preventionField reality
Optical fingerprintLight image of ridges via prismFAR ~0.001% / FRR 1 to 3%Limited, fooled by good latent copiesStruggles with construction workers, dry or worn fingers, dust and outdoor sun
Capacitive fingerprintMeasures charge difference ridge / valleyFAR ~0.001% / FRR 1 to 2%Better, needs live conductive fingerWet hands and ESD sensitive. Keep indoors.
Multispectral fingerprintSurface and sub-surface imagingFAR ~0.0001% / FRR <1%Liveness built inBest fingerprint option for GCC labour camps and plant rooms
3D face (NIR + visible)Depth map plus IR textureFAR 1 in 1,000,000 / FRR <1%Rejects photos, screens, most masksFast, touchless, handles glasses. Check backlight at glazed lobbies.
IrisNIR image of iris patternFAR 1 in 1,000,000+ / FRR ~1%Strong with livenessData centres and vaults. Slower enrolment, user positioning matters.
Palm veinNIR absorption by venous bloodFAR 0.00008% / FRR 0.01%Very strong (internal feature)Hygienic, contactless models available. Higher cost per reader.
Data protection: biometric templates are special category / sensitive personal data. GDPR Article 9 in Europe, UAE Federal Decree-Law No. 45 of 2021 (PDPL), DIFC Data Protection Law No. 5 of 2020 and the Saudi PDPL all apply depending on location. Spec requirement: store templates on card or in encrypted form, never raw images, written consent at enrolment, defined retention and deletion on leaving.

FAR / FRR threshold trade-off

Move the match threshold. Raising it lets fewer impostors in (FAR down) but rejects more genuine users (FRR up). The crossing point is the Equal Error Rate.

3. Complete Door Hardware & Locking Mechanics

Pick a device. You get the holding force, the fail mode, real current figures at 12 V and 24 V, and the mounting details I check on site. Most lock failures I see are not the lock, they are alignment, the wrong bracket, or the door closer fighting the lock.

Holding force vs side load

Maglock ratings are tested pulling straight off the magnet face. In real life the door is pushed at the lever position, with leverage about the hinges. Use this to see what a person at the handle can actually do.

F_push_max = F_rated x k_alignment x (d_lock / d_push) Effective holding (kg) = rated kg x k_alignment ; torque balance about hinge line

Mounting accessory selector

4. Door Auxiliary Devices (DPS, REX, Break-Glass)

The lock gets all the attention in design reviews, but the small devices decide whether the door is safe and whether the head-end knows what is going on. A door with no DPS cannot report forced or held open. A maglock with no hardwired break-glass is a Civil Defence failure.

Door Position Switch (DPS)

  • Surface magnetic contact: retrofit, visible, cheap. Gap rating 15 to 25 mm.
  • Heavy-duty surface contact: armoured lead, roller shutters and loading bays, gap up to 75 mm.
  • Flush recessed contact: drilled into frame head, preferred for new builds, tamper resistant.
  • Roller / plunger switch: mechanical, for doors where magnet alignment drifts.
  • High-security balanced contact: multiple reed switches balanced against a bias magnet, defeats external magnet attack. Needed for Grade 3 / 4 areas.

Request-to-Exit (REX)

  • PIR REX (curtain pattern): mounted above the door on the secure side, aimed down the door face. Shunts DPS so exiting does not trigger forced door.
  • Touchless optical button: IR proximity, hygienic, common in healthcare and offices.
  • Mechanical push button: green "Push to Exit", with timer module or controller timing. For maglocks it must break lock power directly as well as signal.
  • Lever / handle switch: microswitch in mortise lock, best REX for strike-locked doors because egress is always mechanical.

Emergency Break Glass (EBG)

  • Green resettable call point, "Emergency Door Release".
  • Double pole changeover: Pole 1 is in series with lock power and cuts it directly. Pole 2 signals the controller input so the event is logged.
  • Signal-only EBG relies on the controller to release. If the controller has crashed or the cable is cut, the door stays locked. Not acceptable on any egress door.
  • Mount 1.0 to 1.2 m AFFL on the egress side, within reach of the door. Confirm the exact height with the local authority drawing review.

Egress test bench

Set up the door the way the contractor wired it, then try to get out. This is the test the Civil Defence inspector does.

5. Interactive 2D Single-Door Cable Diagram

A typical secure single door: OSDP reader outside, maglock on header, DPS in frame, PIR REX and exit button inside, green break glass in series with lock power, all landed on a 2-door intelligent controller with a separate 12 V DC lock PSU that drops on fire alarm. Click any device or terminal for the terminal designation, cable type and the faults I usually find.

Live trace:

Select a device

Every node is clickable.

Fault injection

Cable schedule for this door

6. Multi-Door & Riser Topology Visualizer

Size the controllers floor by floor and see the riser. RS-485 buses need a 120 Ohm resistor at each physical end only, a daisy chain (never a star), and should stay within 1,200 m and 32 unit loads. IP edge controllers on PoE+ remove the RS-485 problem but move the risk to the network switch and its UPS.

7. Interactive Anti-Passback (APB) Simulator

Anti-passback stops one card being handed back through the fence to let a second person in. It only works if every way in and out of the area has a reader, which is why it is a design decision, not a software tick box. Pick a mode, pick a person and present their card at a reader.

8. Mantrap / Airlock Interlocking Simulator

A mantrap only lets one door be unlocked or open at a time. The interlock is decided on door position (DPS) and lock sense, not just on "the other door is not unlocked". Try the faults: a jammed DPS should make the interlock refuse, not guess.

9. High-Rise Elevator Access Control (Low-Level vs HLI)

Lift access control limits which floors a card can select. Two ways to do it: low-level, where a relay per floor per car sits in series with each COP button through the travelling cable, or high-level interface (HLI), where the access server talks to the lift group controller or destination dispatch system over a software API. Either way, fire service and recall must override access control every time.

Low-level vs high-level: what to write in the spec

ItemLow-level relay interfaceHigh-level interface (HLI)
HardwareRelay boards in each car or machine room, one dry contact per floor per car, in series with COP button commonGateway or server-to-server link, no relays at the COP
Travelling cableNeeds spare cores per car (reader data, power, and relay commons if relays are in the controller room). Check spare cores before awarding.Only the reader cable, or none if readers sit at lobby DCS terminals
Destination dispatchNot practical. DCS has no floor buttons in the car.Native. Card at the DCS terminal books allowed floors only. Lift vendor publishes the API (for example a JSON / REST or vendor SDK).
Fire recallLift controller fire input must bypass relays. Relays should be wired so that loss of power enables all buttons (fail-safe to free access) unless the client accepts otherwise.Lift controller ignores access commands in fire mode. Confirm in the interface matrix.
Who owns the riskELV contractor, with lift vendor approval of the wiring interfaceLift vendor and ELV contractor jointly. Get the interface control document signed early, licences are often extra.

10. Turnstiles, Speed Gates & Barrier Lane Calculator

Lane count is the number architects always get wrong because they size for population, not for the morning peak. Size for the busiest five minutes, use the gate's real throughput with your reader's processing time, then add the accessible wide lane on top.

TypeTypical throughput (persons/min)Security levelLane widthWhere it fits
Optical speed gate (glass swing)25 to 35Medium, tailgate detection by beam arrays600 mm standard, 900 to 1000 mm wide laneGrade A office lobbies
Flap barrier (retractable)30 to 40Medium550 to 650 mm, 900 mm wideMetro, universities, large offices
Tripod turnstile20 to 30Low to medium, easy to climb500 mmLabour camps, factories, stadium outer gates
Full-height turnstile12 to 20High, one person per rotationSingle or double rotorSite perimeters, data centres, ports
Security revolving door / portal6 to 12Very high, weight or 3D sensingDrum 1.6 to 2.4 mBanks, data halls, government

Lane calculator

11. Advanced Lock Power & Voltage Drop Calculator

Low voltage locks are less forgiving than people think. A 12 V maglock on a 60 m run of 0.5 mm² may only see 10 V, and holding force drops roughly with the square of voltage. Enter the devices on one cable run from the PSU and check what the far device actually gets.

Devices on this run

R20 (ohm/km) = 17.241 / A(mm2) ; R_T = R20 x [1 + 0.00393 x (T - 20)] R_loop = 2 x L x R_T / 1000 ; V_d = I_total x R_loop ; V_device = V_supply - V_d Holding force ratio (maglock) = (V_device / V_nominal)^2 , capped at 100%

Conductor size comparison at this load

12. Power Supply (PSU) & Battery Standby Sizing

Size the lock PSU on continuous load plus inrush and spare, then the battery on the autonomy the spec or authority asks for. Remember the trick of access control: fail-safe maglocks draw current all day while locked, so they dominate standby. Fail-secure strikes draw only when released.

Loads on this PSU

I_standby = sum(qty x I_quiescent) ; I_peak = sum(qty x I_active) + largest inrush step PSU rating >= max(I_standby, I_peak) x (1 + spare) Ah = [I_standby x t_autonomy + I_alarm x t_alarm] x ageing x temp factor

13. Intrusion Detection Systems (IDS) Integration

Access control knows who opened a door. Intrusion detection knows someone is in a space that should be empty. On most GCC commercial projects the two are integrated so arming an area locks its doors, and a valid card at the area entry reader disarms it.

DetectorPrincipleBest useCommon false alarm source
PIRPassive infrared, detects moving heat source across zonesOffices, corridorsAC diffuser blowing on it, sunlight on glazing, mounted above a heater
Dual-tech (PIR + microwave)Both technologies must agree (AND logic)Warehouses, plant rooms, hot spacesMicrowave range set too high, sees through drywall into corridor
Acoustic glass-breakListens for flex frequency then shatter frequencyShopfronts, ground floor glazingLaminated glass not covered, heavy curtains blocking sound
Seismic / shockDetects vibration of drilling or cuttingVaults, ATM, safes, server cagesMounted on wall with nearby plant vibration
Active IR beamsBeam interruption between transmitter and receiverPerimeter, fence lines, roof accessBirds, fog, misalignment after wind, sand storms in the GCC
Door / window contactReed switch and magnetEvery perimeter openingPoor alignment, loose doors in high wind

Zone types

Zone typeBehaviour
Entry / ExitStarts entry delay when armed. Usually the main door contact.
Perimeter (instant)Instant alarm when armed. Windows, fire exit doors.
Interior followerInstant alarm when armed, but follows entry delay if the entry zone opened first (the path from the door to the keypad).
Interior (stay bypass)Bypassed in Stay / Part arm so people can move inside.
24-hour silent panicAlways active, never sounds locally, sends to ARC or control room.
24-hour tamperAlways active, detector cover, cable cut, panel lid.

Keypad and zone simulator

DISARMED

14. EOL / DEOL / TEOL Tamper Circuit Visualizer

End-of-line resistors let the panel tell the difference between a contact opening, a cable being cut and a cable being shorted. They only work if they are fitted at the device, not across the panel terminals. I fail this on site more often than any other intrusion item.

Truth table for this configuration

15. Fire Alarm System (FAS) Life-Safety Interlock

On fire alarm, every electrically locked door on an escape route must release. The release must be hardwired: a monitored FAIM relay that drops lock power (or the PSU fire input), not a software message to the access server. Software-only release fails the moment the network, server or controller is down, which is exactly what can happen in a fire.

Fail-safe vs fail-secure override matrix

DoorNormalFire alarmPower lossNotes
Main lobby entrance (escape route)Card / scheduleReleased, free egressReleasedMaglock or EL panic. Hardwired FAIM release.
Stair door, office sideCard from stair side for re-entryReleased both sidesReleasedStair re-entry rules apply in high-rise. Mechanical egress always toward stair.
Fire rated door with strikeCardFree egress by lever, latch stays engagedFree egress by leverFail-secure strike so the door still latches for fire integrity. Egress is mechanical.
Server / data roomCard + PINEgress free, entry stays secured (client decision with AHJ)Egress free by leverNever lock someone inside. Exit side is always free.
Cash office / vaultDual custodyEgress free, entry securedEgress freeFail-secure entry hardware, mechanical free egress.

Code references for egress with electric locking

ReferenceWhat it asks for (summary, verify against current edition)
NFPA 101 - Sensor-release of electrical locking systemsSensor on egress side releases the lock on approach. Loss of power releases. Manual release device within 1,525 mm (60 in) of the door, 1,015 to 1,220 mm (40 to 48 in) AFF, signed "PUSH TO EXIT", releasing independent of the electronics for at least 30 s. Fire alarm or sprinkler activation releases.
NFPA 101 - Delayed egress lockingOnly where the occupancy allows. Releases after 15 s (30 s if the AHJ approves) of sustained push, irreversible process, local alarm, released on fire alarm and power loss, signage on the door.
BS 7273-4Categorises the actuation of door release mechanisms by risk (Category A, B, C). Defines how the fire alarm signal must reach the lock power, monitoring of the interface and fail-safe behaviour.
UAE Fire & Life Safety Code (Civil Defence)Means of egress chapter: electrically locked doors on escape routes release on fire alarm and loss of power, with a manual release at the door. Confirm local DCD requirements at design NOC stage.
BS EN 13637 / BS EN 1125 / BS EN 179Electrically controlled exit systems, panic exit devices, emergency exit devices. The hardware on the door must be certified for the escape route type.

16. Visitor Management & Barrier Automation

Visitors are where most access systems leak. A good flow pre-registers, verifies ID, issues a time-limited credential that only opens the host's floor, and expires it automatically. For vehicles, ANPR handles visitors and UHF tags handle regular staff at speed.

TechnologyRead rangeSpeedWeaknessUse for
QR code (static)Contact to 20 cm1 to 2 sScreenshots shared, replayableEvents, low risk
QR code (dynamic, rotating)Contact to 20 cm1 to 2 sNeeds app or wallet passVisitor and staff mobile access
ANPR camera3 to 15 m0.3 to 1 s per plateDirty or non-standard plates, glare, cloned platesVisitors, deliveries, car park billing
UHF RFID windscreen tag (860 to 960 MHz)Up to 10 mFree flowMetallised windscreens block it, needs a tag per carStaff and residents, VIP lanes
Long-range BLEUp to 10 m1 to 2 sPhone must be on and app runningResidential car parks

ANPR barrier simulator

17. Biometric & Multi-Factor Access Logic Builder

Assign a security level to each door and test it. Factors are something you have (card), something you know (PIN) and something you are (biometric). Dual custody adds a second authorised person inside a time window. Every factor you add costs throughput, so put the strong modes only where the risk justifies it.

Person 1

Person 2 (dual custody)

Duress PIN grants access as normal so the person is not put at risk, but raises a silent priority alarm at the control room. Specify it, and train guards on what to do with it.

18. Interactive 2D Security Floor Map

A typical office floor with readers, door contacts, PIRs, window contacts, panic buttons and cameras. Run a scenario or click any device to trigger it. Watch the alarm stack the way a control room operator sees it, acknowledge, then clear. Linked cameras pop up automatically.

Floor intrusion: Scenarios:
CAM - no call-upREC

Alarm stack

No active alarms.

19. 3D Hardware Inspection Viewer: Intelligent Door Controller Cabinet

Drag to rotate the enclosure, open the door and explode the backplate to see each component. This is the cabinet I open at every inspection: I check the PSU output setting, the battery date and voltage, the tamper switch, earth bonding of the door and the labelling of every field terminal.

Rotate: drag, or use the sliders

Click a component

Every coloured block on the backplate is clickable.

Cabinet inspection points

CheckAcceptance
PSU output voltage (no load and full load)13.6 to 13.8 V on 12 V systems, 27.2 to 27.6 V on 24 V systems
BatteryDate label within 4 years, terminal voltage above 12.6 V each block after charge, no swelling, correctly fused lead
Tamper switchOpening the door raises a tamper alarm at the head-end within seconds
Fire alarm interfaceFAIM relay or PSU fire input wired, monitored, labelled, tested with the FA contractor present
EarthingEnclosure and door earth bonded, cable screens terminated at the panel end only
LabellingEvery field cable ferruled, terminal schedule taped inside the door, as-built matches

20. 4D Operational & Time-Based Access Simulation

Time is the fourth dimension of an access system. Doors change state through the day on schedules, holidays override them and night lockdown closes everything. Press play and watch a full 24 hours. The "first person in" rule keeps the main entrance locked until a valid staff card has been used, so a snow day or a public holiday does not leave the lobby open to the street.

21. Testing & Commissioning (T&C) Master Dashboard

The 25-point SAT list I use for access control handover. Tick items as they are witnessed, add remarks for anything that fails, sign off at the bottom and export. Your ticks are saved in this browser.

0%

Sign-off

22. Field Troubleshooting & Maintenance Guide

The faults that actually generate call-outs, in the order I would check them. Filter by symptom or keyword.

Planned preventive maintenance

FrequencyTask
MonthlyReview head-end for offline devices, forced and held-open trends, battery trouble events. Remove leavers.
QuarterlyWalk test sample of doors: card, REX, DPS, EBG. Clean maglock faces. Check closers.
Six-monthlyPSU output and battery discharge test. Fire alarm release test with the FA contractor.
AnnuallyFull door audit, firmware review, database backup restore test, credential audit, penetration review of controller network.

23. SIRA (Dubai), GCC Authority & International Codes

Security systems in the GCC are approved by the security authority as well as Civil Defence. Get the authority category for the building early, because it fixes camera counts, recording days, access control and intrusion requirements, and the approved contractor list. The table below is a working summary; always read the current edition issued by the authority.

Authority manuals and codes are updated regularly and differ by building category. Use this table to know what to look for, then confirm clause numbers and requirements against the latest document from SIRA, the relevant Civil Defence directorate, or the standards body before design sign-off.

24. Comprehensive Master Quiz

30 questions across the whole lab. Answer each one to see the explanation straight away. Your score updates as you go.

25. Exportable Engineering Submittal & Cable Schedule

This sheet pulls the live results from the riser (Tab 6), lift (Tab 9), turnstile (Tab 10), lock Vd (Tab 11), PSU and battery (Tab 12) and T&C (Tab 21) calculators. Change any input there and come back, or press refresh. Print or save as PDF from your browser.

About this lab: Access Control & Physical Security Engineering Master Lab

Access Control & Physical Security Engineering Master Lab

Learn access control design: OSDP vs Wiegand, door hardware, maglock voltage drop, PSU and battery sizing, anti-passback, lifts, fire release and SIRA rules.

Topics you can explore

  • Access control system architecture (2-tier, 3-tier, cloud)
  • OSDP vs Wiegand reader wiring
  • Maglock, electric strike and panic hardware selection
  • Lock power voltage drop and PSU battery sizing
  • Anti-passback, mantrap and lift access control
  • EOL / DEOL / TEOL intrusion circuits and fire alarm door release
  • SIRA, Civil Defence, BS EN 60839-11-1, UL 294 and NFPA 101

Practical engineering example

A 12 V maglock drawing 0.5 A on 60 m of 0.5 mm2 cable at 45 deg C loses about 2.3 V. On battery at 10.8 V it sees about 8.5 V, roughly half its holding force. Upsize the cable or add a local PSU, then confirm the voltage at the lock during the SAT.

Developed by Eng. Mannan Maqsood. Verify design outputs against current project requirements and the applicable authority and manufacturer data.

NEXT STEP

Where to go from here

Related labs that pick up where this one ends, and a learning path to follow.

CCTV, Access Control & SecurityCompanion lab: CCTV design, access control basics and security integration.ELV-303 →CCTV Video Surveillance System LabCamera selection, storage sizing and video analytics for the cameras your doors call up.ELV-305 →Fire Alarm System Virtual LabLoops, addressing and cause and effect, including door release outputs.FA-201 →Site Engineering TrackInstallation, inspection, submittals, snags and testing in 6 labs.LEARNING PATH →