Size 11 kV to 33 kV XLPE cables properly: current rating with the IEC 60287 method, a live soil heat map, conductor and screen short-circuit checks, voltage drop, screen bonding, cleat forces and lifetime losses. Change the soil, depth or bonding and watch every number and view update. Click any for a plain-language explanation.

IEC 60287IEC 60502-2IEC 60949IEC 61914AS/NZS 1429.1BS 6622

1. Cable and site data

Pick your region first. It loads the utility voltages, typical ratings, ambient, fault level, phase colours and standards. Everything can be changed.

Click any layer
Drag to rotate, scroll or pinch to zoom. The conductor glows hotter as the load rises.

Engineer's Notes: sizing HV cables

Heat is the real limit

An XLPE cable can run its conductor at 90 °C continuously. Everything that slows heat leaving the cable lowers its rating: hot ground, dry soil, deeper laying, ducts, neighbouring circuits and screen losses. That is why a cable that is fine in Auckland can overheat in Dubai at the same current. Always rate with the utility design conditions.

Three separate checks

A cable size has to pass three tests: continuous current rating, short-circuit withstand of the conductor and the screen, and voltage drop. On short HV feeders in buildings the short-circuit or screen check often decides the size, not the load.

Screens and bonding

The copper screen carries earth fault current and capacitive charging current. How you bond it changes the rating: solid bonding is simple but adds circulating current losses on large single-core cables. Single-point and cross bonding remove those losses but need standing voltage control, sheath voltage limiters and link boxes.

Hold the cables together

Fault currents throw single-core cables apart. Trefoil cleats rated to IEC 61914 and spaced correctly keep them in place. The forces climb with the square of the peak current, so a 50 kA peak can produce more than 10 kN per metre.

Frequently asked questions

Why is the same HV cable rated lower in the GCC than in New Zealand?

Current rating depends on how fast heat leaves the cable. GCC ground temperatures of around 35 degrees C at cable depth and dry sand with high thermal resistivity leave less temperature headroom and slow heat flow, so the same 240 mm2 cable can carry 20 to 30 percent less than in cool, moist New Zealand soil.

How is the copper screen of an HV cable sized?

The screen must carry the network earth fault current for the protection clearing time without overheating its insulation. With the adiabatic method of IEC 60949, the required area is the fault current times the square root of the time, divided by a factor k for copper between the operating and maximum screen temperatures.

What is the difference between solid, single-point and cross bonding?

Solid bonding earths the screens at both ends: simple and safe, but circulating currents heat the screens and reduce the rating of large single-core cables. Single-point bonding earths one end only, removing circulating currents but leaving a standing voltage at the open end. Cross bonding transposes the screens at link boxes so induced voltages cancel over each major section.

What is the standing voltage limit on single-point bonded cables?

It depends on the utility and standard. Values of around 50 to 65 V under full load are common limits for touchable screen ends, with sheath voltage limiters fitted to handle faults. Longer routes use cross bonding instead.

Why do single-core HV cables in trefoil need cleats?

During a short circuit, the three cables repel each other with large electromagnetic forces. IEC 61914 estimates the force per metre as 0.17 times the square of the peak fault current in kA divided by the centre spacing in metres. Cleats must be rated for that force and spaced close enough to hold the cables.

Topics: IEC 60287 current rating · soil thermal resistivity · ground temperature · grouping factors · ducts · cables in air · screen short circuit · IEC 60949 · voltage drop · solid bonding · single-point bonding · cross bonding · standing voltage · cleat force IEC 61914 · cable losses

Related labs

NEXT STEP

Where to go from here

Related labs that pick up where this one ends.

HV Academy hubAll 17 high voltage labs in one learning path.HV ACADEMYDistribution Transformer Design & Installation LabSize distribution transformers, check losses, vector groups, taps and IEC 60076-7 hot-spot ageing, with 2D,…HV-504 · previousFault Level & Short Circuit LabCalculate HV and LV fault levels to IEC 60909: peak, breaking and thermal currents, switchgear ratings,…HV-506 · nextMV Cables & Accessories LabMV XLPE cable lab: 3D cable layers, IEC 60287 rating for 6.6 to 33 kV, voltage drop and short-circuit checks,…MV-502 · MV view
Track what you have opened on My progress.All labs → · Ask the Copilot →

© 2026 Eng. Mannan Maqsood | Engineering Excellence Through Interactive Labs

VERIFY ALL FIGURES AGAINST CURRENT MANUFACTURER DATASHEETS AND LOCAL AUTHORITY REQUIREMENTS BEFORE DESIGN SIGN-OFF.

Share this pageFollow