PLB-701 · PLUMBING · COLD WATER

Water Demand & Booster Pump Lab

Count the fixtures, convert them to water supply fixture units and a probable peak flow with the Hunter curve, then size the booster set: pressure zones that keep every outlet between the minimum and maximum pressure, pump duty, power and the riser size. Play a day of demand to see how the pumps stage.

IPC Appendix EUPCDubai Building CodeBS EN 806AS/NZS 3500.1NZBC G12

How to use: enter fixtures per typical floor and the number of floors. Fixture unit values are typical IPC figures you can edit. Tap i for explanations.

1. Building and fixtures

Fixtures per typical floor, all floors alike.

Building
Fixtures per floor
Pressure and pumps

2. Pressure zones

Static pressure on every floor with zones and pressure reducing valves marked.

3. Checks

    4. Demand and zones

    5. How it works

    Fixture units and the Hunter curve

    Every fixture gets a water supply fixture unit (WSFU) value reflecting how much and how often it draws. The total does not add up linearly: the chance of all taps running at once falls as the number grows. The Hunter curve turns total fixture units into a probable peak flow, which is what pipes and pumps are sized for.

    Pressure zones

    Every outlet needs enough pressure to work (shower mixers about 1 to 1.5 bar, flush valves more) and no more than the maximum (5 bar in AS/NZS 3500.1 and common UAE practice) to avoid noise, splashing and wear. Height adds 0.0981 bar per metre, so a tall building is split into zones, each with its own pump set or pressure reducing station.

    Booster set

    Variable speed booster sets with several pumps cover the peak with one standby and run one small pump most of the day. Pump power is flow × head / efficiency.

    Learning and checking tool. Use the fixture values and method your authority adopts, for example the Dubai Building Code, IPC, BS EN 806-3 or AS/NZS 3500.1.

    About this lab: Water Demand & Booster Pump Lab

    Water Demand & Booster Pump Lab

    Turn fixtures into fixture units and a probable peak flow with the Hunter curve, then size booster pumps, pressure zones, PRVs and risers for a high rise building.

    Topics you can explore

    • Water supply fixture units
    • Hunter curve
    • Minimum and maximum outlet pressure
    • Pressure zones
    • Pressure reducing valves
    • Booster pump sets with VSD
    • Riser velocity

    Practical engineering example

    A 30 floor residential tower with six WCs, six basins, four showers, two baths and three kitchen sinks per floor adds up to about 1,430 fixture units, or about 16.5 L/s on the Hunter curve. Keeping outlets between 1.5 and 5 bar means three pressure zones of ten floors, and the top zone pumps need about 118 m of head.

    Developed by Eng. Mannan Maqsood. Verify against current project requirements and the applicable authority rules.

    Standards and regions covered

    Built around IPC Appendix E and UPC fixture unit methods used with the Dubai Building Code, BS EN 806, AS/NZS 3500.1 and NZBC G12. Engineers use it on projects in Dubai, Abu Dhabi, Sharjah and the Northern Emirates, Saudi Arabia and Qatar, and in Auckland, the rest of New Zealand and Australia. Always confirm the edition your authority or client has adopted before relying on a result.