PLB-703 · PLUMBING · DRAINAGE

Drainage Stack & Building Drain Lab

Add up the discharge units of the fixtures, apply the frequency factor and size the soil stack to BS EN 12056-2, with or without a secondary vent. Then size the building drain by slope and fill with Colebrook-White, check self cleansing velocity, and watch a flush travel down the stack.

BS EN 12056-2BS EN 752Dubai Building CodeIPC chapter 7AS/NZS 3500.2NZBC G13

How to use: enter fixtures per floor and floors per stack. Discharge units are the BS EN 12056-2 System I values and you can edit the counts. Tap i for explanations.

1. Stack and fixtures

One stack serving the same fixtures on every floor.

Building
Fixtures per floor
Building drain

2. Stack and drain

Stack loading against capacity, the drain cross section at design flow, and a flush in 4D.

3. Checks

    4. Drain sizes at your gradient

    5. How it works

    Discharge units and K

    Each fixture has a discharge unit (DU) in L/s. They are not simply added: the wastewater flow is Qww = K × √ΣDU, where K reflects how often fixtures are used. The flow can never be less than the largest single fixture.

    Stack capacity

    A stack carries water as a film on the wall with an air core in the middle. Too much water closes the core and pulls the water seals out of the traps. BS EN 12056-2 tables give the capacity of each stack size for primary or secondary ventilation and for square or swept junctions.

    Building drain

    Horizontal drains are sized with Colebrook-White for the gradient, running no more than half full (h/d 0.5) so air can move, and at least 0.7 m/s so solids are carried along.

    Learning and checking tool. Some authorities use IPC or AS/NZS 3500.2 fixture units instead of discharge units. Use the method your authority adopts.

    About this lab: Drainage Stack & Building Drain Lab

    Drainage Stack & Building Drain Lab

    Size soil stacks with BS EN 12056-2 discharge units, frequency factor and stack capacity tables, then size the building drain by gradient and fill with Colebrook-White.

    Topics you can explore

    • Discharge units
    • Frequency factor K
    • Stack capacity tables
    • Primary and secondary ventilation
    • Swept and square junctions
    • Building drain gradient
    • Proportional depth and velocity

    Practical engineering example

    A 25 floor apartment stack with two WCs, two basins, two showers, a kitchen sink, dishwasher, washing machine and floor gully per floor adds up to 265 DU, or about 8.1 L/s at K 0.5. That needs a DN150 primary ventilated stack, or a DN125 with a secondary vent and swept junctions.

    Developed by Eng. Mannan Maqsood. Verify against current project requirements and the applicable authority rules.

    Standards and regions covered

    Built around BS EN 12056-2 and BS EN 752 as used with the Dubai Building Code, with notes for IPC chapter 7, AS/NZS 3500.2 and NZBC G13. Engineers use it on projects in Dubai, Abu Dhabi, Sharjah and the Northern Emirates, Saudi Arabia and Qatar, and in Auckland, the rest of New Zealand and Australia. Always confirm the edition your authority or client has adopted before relying on a result.