What causes harmonics?
Non-linear loads draw current in pulses instead of a smooth sine wave. Variable speed drives, UPS rectifiers, LED drivers, IT power supplies and EV chargers are the big sources in buildings. That current, flowing through the supply impedance, distorts the voltage for everyone on the same supply. Harmonics cause extra heating in transformers and cables, neutral overloading from triplen (3rd, 9th) harmonics, nuisance tripping and capacitor failures.
PractitionerChoose drives with DC chokes or AC line reactors (or active front ends) for large loads, size neutrals for triplen harmonics in IT-heavy buildings, and specify K-rated or derated transformers where THD is high. Measure at the main LV board during commissioning with a class A power quality analyser.
Why do capacitor banks need detuning?
A capacitor bank in parallel with the transformer's inductance forms a tuned circuit. Its parallel resonance order is about √(Ssc/Qc). As steps switch in, that resonance moves, and it often passes through the 5th and 7th harmonics. Harmonic currents near the resonance are amplified, raising voltage distortion and overloading the capacitors. Adding a series reactor (7% is the most common, 14% where 3rd harmonics are significant) moves the bank's own tuning below the lowest major harmonic, so the bank looks inductive to the harmonics and cannot amplify them.
ExpertA reactor in series raises the voltage across the capacitor by 1/(1 − p), about 7.5% for p = 7%, so capacitors in detuned banks must be rated for a higher voltage (for example 480 V or 525 V units on a 400 V system), and the effective kvar at 400 V must be checked.
Regional notes
GCC
Utilities set a minimum power factor at the point of supply in their regulations and can apply penalties. Large chiller plants with VFDs make detuned banks and harmonic filters common in GCC buildings.
Australia and New Zealand
Network operators apply AS/NZS 61000.3.6 style allocation of harmonic limits and set minimum power factor requirements in their service rules.
Asia
Utilities such as TNB publish power factor and harmonic requirements in their supply guidelines, often based on IEC 61000 and IEEE 519.