Why monitor MV equipment condition?
Most MV equipment fails slowly before it fails suddenly. Oil gases build up, joints heat up, and partial discharge erodes insulation over months. Condition monitoring catches these early signs so that repairs can be planned during an outage instead of after a fault. The key is trending: one result tells you little, but a rising trend tells you a lot.
Reading DGA results
- Hydrogen with little else suggests partial discharge.
- Methane and ethane point to lower-temperature overheating. Ethylene rises with hotter faults.
- Acetylene means arcing or very high temperatures. Treat any rise as urgent.
- CO and CO2 come from paper insulation. A CO2/CO ratio below about 3 suggests the paper itself is being overheated.
ExpertUse the Duval triangle only when gas levels are above typical values or rising, otherwise normal background gases can land in a fault zone. IEC 60599 and IEEE C57.104 give typical concentration and rate-of-increase values. Duval pentagons and triangles 4 and 5 help separate overlapping thermal faults.
Thermography good practice
Survey at high load, with the covers removed only where safe and permitted, and use an emissivity setting suited to the surface. Compare similar components (the three phases of the same termination) rather than relying on absolute temperature. Record load, ambient and distance with each image.
Regional notes
GCC
High ambient temperatures and dust make thermography and connection checks especially important before summer peaks. Coastal humidity and salt drive surface tracking on terminations.
Australia and New Zealand
Distributors run condition-based maintenance programmes with online PD and DGA for zone substation assets, and seismic events can loosen connections, so post-event inspections are common in New Zealand.
Asia
Large urban cable networks use online PD monitoring and periodic DGA, with tropical humidity a common contributor to termination failures.