What tests are done on an MV installation before energising?
- Visual and mechanical: nameplates against the approved submittals, torque marks, clearances, earthing connections, interlocks, gas pressure gauges.
- Cables: insulation resistance of the core and the oversheath, a withstand test (often VLF at about 3 U0, or as the utility specifies), optional tan delta and partial discharge diagnostics, and phasing end to end.
- Transformers: insulation resistance, turns ratio on every tap, winding resistance, vector group check, oil tests for oil-filled units, and protection devices (temperature, gas or pressure relays).
- Switchgear: insulation resistance, contact resistance, timing on breakers, interlock function, VPIS checks.
- Protection: CT ratio, polarity and magnetisation checks, secondary injection of every relay, and trip tests to the breaker.
- Earthing: earth resistance and continuity, and for larger sites, touch and step measurements.
PractitionerRecord the instrument serial and calibration date, temperature and humidity, and the test voltage and duration for every result. Insulation resistance changes a lot with temperature, so correct readings to a reference temperature (usually 20 °C) before comparing them.
How do you read VLF tan delta results?
Tan delta measures the losses in the insulation. Healthy XLPE has very low, stable tan delta that barely rises with voltage. Water trees make tan delta rise with voltage (high tip-up). Contaminated or wet joints and terminations make readings unstable. IEEE 400.2 combines the mean at U0, the standard deviation (stability) and the difference between 1.5 U0 and 0.5 U0 (tip-up) into three classes: no action, further study, and action required.
ExpertTan delta is an average over the whole cable length. A single bad joint on a long route can be hidden by many metres of healthy cable, so add partial discharge testing with location where joints are a concern.
Regional notes
GCC
Utilities usually witness MV cable tests and pre-energisation checks and have their own test formats and voltages. High site temperatures affect insulation readings, so record the temperature and correct.
Australia and New Zealand
Network operators specify cable test methods and voltages, with VLF and tan delta widely used. AS/NZS 3017 and AS/NZS 3019 cover verification of LV installations.
Asia
Utilities such as TNB and SP Group publish test and commissioning requirements and witness the tests before energisation.