MV-505 · Phase 2 Design & analysis

Substation Design & Layout 3D

Size a substation room for your RMU, transformers and LV board, see the layout in 3D with live clearance checks, work out ventilation and oil containment, then play the build week by week.

In short

  • A distribution substation room holds the RMU, one or more transformers, the LV main board and the cable trench, with access for delivery and safe operation.
  • Keep a clear operating aisle in front of switchgear. IEC 61936-1 sets minimums of about 0.8 m, and many utilities ask for 1.0 m or more.
  • Natural ventilation inlet area is roughly S = 0.18 P / √H (m²), where P is the transformer losses in kW and H is the height between inlet and outlet in m.
  • Oil-filled transformers need oil containment sized for at least the full oil volume, and an indoor room usually needs fire-rated walls and doors.
  • The utility's standard substation drawings and the local fire code have the final say on dimensions.

3D Substation Designer 3D Checks

Set the room and equipment. The 3D layout updates and the floor zones turn green or red as each clearance passes or fails. Drag to rotate and click equipment for details.

Drag: rotate · Wheel/pinch: zoom · Click: inspect
Layout result

    Click equipment

    Click the RMU, a transformer, the LV board, the trench or a clearance zone to learn what it needs.

    Transformer Room Ventilation 2D Animated

    Heat from the transformers has to leave the room. Cool air comes in low, warm air leaves high. Change the inputs to see whether natural ventilation is enough or fans are needed.

    4D Construction Sequence 3D 4D

    Scrub through the build week by week, from slab and trench to energisation. Each stage lists the hold points to check before moving on.

    Week 1 ·

      What goes into a distribution substation room?

      A typical building substation in the GCC has an 11 kV RMU, one or two 11/0.4 kV transformers, an LV main switchboard (sometimes in a separate LV room), a cable trench or basement for MV and LV cables, an earthing system, ventilation and fire protection. The utility usually owns the RMU and transformers, and the building owns the LV board, so the room has to work for both: utility access from outside, and safe operation for both teams.

      PractitionerCheck the utility's standard room drawing first. It fixes the room size for each transformer combination, the door positions, trench layout, louvre sizes and equipment plinths. Designing your own room and asking the utility to accept it later is the usual cause of redesign.

      What clearances do MV and LV equipment need?

      • Operating aisle in front of the RMU and LV board, so an operator can stand clear and the door or panel can open fully. IEC 61936-1 gives minimum aisle widths around 0.8 m, and utilities often require 1.0 to 1.5 m.
      • Around transformers, room for cooling air and maintenance access, often 0.6 m or more to walls and between units.
      • Delivery route: door and route sized for the largest transformer, with lifting or skating space.
      • Cable trench deep enough for the MV cable bending radius (often 12 to 15 times the cable diameter).

      How do you size transformer room ventilation?

      For natural ventilation, a common first-pass formula from manufacturers' MV design guides is inlet area S = 0.18 P / √H, with the outlet about 10% larger. P is the total transformer losses in kW and H is the height between the centres of the inlet and outlet louvres in metres. It assumes about a 15 K rise in air temperature. For forced ventilation, the airflow is Q = P / (1.2 × 1.005 × ΔT) m³/s. In the GCC, outside air at 45 to 50 °C leaves little headroom, so fans, sand-trap louvres and sometimes cooling are common.

      Oil containment and fire

      An oil-filled transformer can leak or burst. The room needs a bund, pit or drain to a tank that can hold at least the full oil volume, plus allowance for fire water where the code asks for it. Inside buildings, oil-filled transformer rooms are usually fire-separated (often 2 hours) and may need detection or suppression, which is a big reason cast resin units are used in towers.

      Regional notes

      GCC

      Follow the utility's substation room standards (DEWA, ADDC/AADC, SEWA, KAHRAMAA, SEC and others) and the civil defence fire code. Design ventilation for the real outside temperature and dust, and agree access for utility staff.

      Australia

      AS 2067 covers substation design, including clearances, fire segregation and oil containment. Network operators publish their own substation manuals, and pad-mount kiosks are very common.

      New Zealand

      Lines companies set the kiosk and room standards. Seismic restraint of equipment and plinths is designed to NZS 1170.5 and NZS 4219.

      Asia

      Utilities such as TNB and SP Group publish substation room requirements, including room sizes for each transformer arrangement.

      Test yourself

      0 / 8

      8 questions. Pick an answer to see the explanation. Practise about 50 more MV-505 questions in the MV Question Bank.

      Frequently asked questions

      How big should an 11 kV substation room be?
      It depends on the number and size of transformers and on the utility's standard. As a rough guide, a room with one RMU, two 1500 kVA transformers and an LV board is often around 8 to 10 m long and 5 to 6 m wide. Always start from the utility's standard drawing.
      How do I calculate transformer room ventilation?
      For natural ventilation, a common first estimate is inlet area S = 0.18 P / √H m², with the outlet about 10% larger, where P is the losses in kW and H is the height between inlet and outlet in metres. For fans, Q = P / (1.2 × 1.005 × ΔT) m³/s.
      How big should a transformer oil pit be?
      At least the full oil volume of the largest transformer it serves, plus any allowance the code requires for rainwater or fire-fighting water. Take the oil volume from the transformer datasheet.
      What clearance is needed in front of MV switchgear?
      IEC 61936-1 sets minimum aisle widths of about 0.8 m for operation. Many utilities require 1.0 m or more, and the full door or withdrawable unit swing must stay clear.

      Standards referenced

      • IEC 61936-1 Power installations above 1 kV
      • IEC 62271-202 Prefabricated substations
      • AS 2067 Substations (Australia)
      • NZS 4219 Seismic performance of engineering systems
      NEXT STEP

      Where to go from here

      Related labs that pick up where this one ends.

      Medium Voltage hubAll 16 MV labs and the 788-question MV bank.MV HUBDistribution Transformer LabOil and cast resin transformers in 3D, animated Dyn11 vector groups, parallel operation, kVA sizing, losses,…MV-504 · previousShort Circuit & Load Flow StudioIEC 60909 short circuit from the 11 kV source to the final DB: three-phase and earth fault levels, peak…MV-506 · nextPrimary Substations & GIS LabCompare busbar schemes in 4D, GIS vs AIS footprint, SF6 density and leakage, N-1 transformer capacity and a…HV-515 · HV view
      Track what you have opened on My progress.All labs → · Ask the Copilot →

      © 2026 Eng. Mannan Maqsood | Engineering Excellence Through Interactive Labs

      VERIFY ALL FIGURES AGAINST CURRENT MANUFACTURER DATASHEETS AND LOCAL AUTHORITY REQUIREMENTS BEFORE DESIGN SIGN-OFF.